67. Add System Features
* Features 26, 27 & 28 will delay User Codes 12 and higher only (except 297, 298 and 299, and any Emergency Command enabled User).
** Features 30, 31 & 32: Note: Scheduled events and Door Ajar monitoring (and their associated audit trail entries)
will not occur during sustained closure of the re-
mote input. NOTE: Enter ; 6 7 ; 0 0 0 : to delete all Relay Features added by Function 67 (identical to Function 68).
*** Feature 24, "One Time Access for Group 3 Users", allows the creation of multiple 'one time only' User Codes. When activated, an entry by a Group 3 User allows entry
only once, then user becomes disabled. Note: When the User Code is entered for the first time and access is granted, the Event Log will read "Entry" followed by
"User Disabled". If the User Code is entered a second time, access will be denied, and the Event Log will read "User Denied Access".
To Enable the Feature: Enter Program Mode and enter the key sequence ; 6 7 ; 2 4 :.
To assign the selected User Codes to Group 3: For example, to assign User Number 15 to Group 3, press: ; 3 5 ; 1 5 ;
3 :.
Programming Functions (cont'd)
Ambush Function
1. Connect relay to a device able to properly monitor dry contacts for an Ambush condition.
2. Program the Relay for Ambush Tripped using Program Function 67 (Feature 10) above.
3. Set the Ambush Code using Program Function 66.
4. When the Ambush Code is entered followed by a valid User Code (or proximity card), the relay will close for 2 seconds.
Notes: The Ambush Code defaults to 99. An error will sound if you try to program a new User Code starting with the Ambush Code.
Auxiliary Relay Features (14-23 Reserved)
Use Function 67 to program one or more events and the Auxiliary Relay (NETWORXPANEL terminals T16-T18 shown below) will energize for
two seconds (unless otherwise specified) when the programmed event or events listed below occurs. Note: For information about the Remote
Input, see page 21 (Function 65). Delete all Auxiliary Relay Features with Function 68.
4
1. Remote Input switch closed and Function 65
Remote Input enabled. Because the Remote
Input is enabled by factory default, the Aux Relay
will energize when the Remote Input switch is
closed.
2. Remote Input switch closed and Function 64
Remote Input disabled. If the Remote Input is
disabled with Function 64, the Aux Relay will en-
ergize when the Remote Input Switch is closed.
3. Failed attempted entry. Aux Relay energizes for
2 seconds when an attempted User Code entry
(or proximity card / keyfob) fails.
4. Disabled User or Group. Aux Relay energizes for 2 seconds when
a disabled User or disabled Group member enters a User Code (or
proximity card / keyfob).
5. Follow Access Granted. When a valid User Code is entered into the
keypad and the secured door "unlocks", the Aux Relay energizes for 2
seconds. Compare with Event 31.
6. Scheduled Group 1 User Code. Aux Relay energizes for 2 seconds
when a scheduled Group 1 User Code (or proximity card / keyfob) is
entered. See Function 90, page 25.
7. Scheduled Lock Event. Aux Relay energizes for 2 seconds when
the NETWORXPANEL "locks" the secured door by a Schedule.
8. Scheduled Unlock Event. Aux Relay energizes for 2 seconds when
the NETWORXPANEL "unlocks" the secured door by a Schedule.
9. Keypad Lockout. Aux Relay energizes for 2 seconds when a Key-
pad Lockout occurs (i.e. number of attempts is exceeded, see Func-
tion 60).
10. Ambush. Aux Relay energizes for 2 seconds when Ambush is
tripped. See Function 66, page 21.
11. First Key Press or Proximity Credential. Aux Relay energizes for 2
seconds at the first key press of any sequence or upon the presenta-
tion of ANY (enrolled or un-enrolled, enabled or disabled) proximity
card / keyfob.
12. Relay On Door Ajar. If the door is held open for longer then the al-
lowed Door Ajar Time (programmed at function 68) the Aux Relay will
engage for 2 seconds. See "Door Ajar" in glossary.
13. Create Two Door Mode: If this feature is set, all existing Aux Relay
features are erased, and a two-door system ("Two Door Mode") is
created: The primary Alarm Lock keypad addressed as Keypad 1 for
door 1 (or Wiegand device wired to NETWORXPANEL terminal "WO")
will activate the NETWORXPANEL Main Relay. The secondary Alarm
Lock keypad addressed as Keypad 2 for door 2 (or Wiegand device
wired to NETWORXPANEL terminal "WOA") will activate the NET-
WORXPANEL Aux Relay.
Note: When Two Door Mode is enabled, program any other relay
feature will disable Two Door Mode.
31. Follow Access Granted--No Time Limit.** When a valid User Code
is entered and the secured door unlocks, the Aux Relay energizes for
the same amount of time as the programmed Pass Time. (The Pass
Time is the length of time the secured door stays "unlocked" after a
valid User Code is entered. See functions 52-54). Use this feature for
remote monitoring or other activation as this feature works independ-
ently of all other Aux Relay options. Programming this feature will
supersede all other programmed Aux Relay features. Subsequent
Aux Relay feature programming will not take effect while this feature is
active. Before programming any other Aux Relay features,
press
; 6 8 ; 0 0 0 : to delete this fea-
ture.
System Options
24. One Time Access for Group 3 Users***
25. Disable Sounder
26. Five (5) second Delayed Entry *
27. Fifteen (15) second Delayed Entry *
28. Forty-five (45) second Delayed Entry *
Remote Input Functions
29. Toggle Passage Mode. Remote Input toggles Passage Mode.
30. Forced Unlock Follows Remote Input.** When Remote Input
switch is closed, regardless of the current state of the system, the
system "unlocks" for the duration of the Remote Input switch clo-
sure.
32. Remote Input Disables Unit.** Regardless of the current state of
the system, that state will remain unchanged (and keypad will be
disabled) for the duration of Remote Input switch closure.
34. Forced Lock Follows Remote Input ** When Remote Input
switch is closed, regardless of the state of the system, the system
will "lock" for the duration of the Remote Input switch closure.
Enable Emergency Commands
38. Emergency Commands Enable (default = ON)
39. User Lockout on Emergency (default = ON)
Door Ajar
40. Door Ajar Monitor On (default = OFF).
If this feature is set ("ON") and the Door Position Contacts remain
open past the time set at Function 68 "Door Ajar Time" (default is 20
seconds), a Door Ajar Event will be logged. The Aux Relay can
also be programmed for a Door Ajar event (see above feature 12).
See "Door Ajar" in glossary.
41. Door Ajar Alert Sounder On (default = OFF)
If this feature is set, the sounder will sound when the Function 68
"Door Ajar Time" expires. Feature 40 must be set ("ON") for this
Alert Sounder to operate (follows default Door Ajar Time of 20 sec-
onds unless programmed otherwise using function 68).
NETWORXPANEL
Aux Relay Terminals
N/O N/C COM